Publication:
Tube side heat transfer coefficient and friction factor characteristics of horizontal tubes with helical rib

dc.contributor.authorNaphon P.
dc.contributor.authorNuchjapo M.
dc.contributor.authorKurujareon J.
dc.date.accessioned2021-04-05T04:32:18Z
dc.date.available2021-04-05T04:32:18Z
dc.date.issued2006
dc.date.issuedBE2549
dc.description.abstractThe results of the heat transfer and pressure drop characteristics in horizontal double pipes with helical ribs are presented. Nine test sections with different characteristic parameters of: helical rib height to diameter, χ/di = 0.12, 0.15, 0.19, and helical rib pitch to diameter, p/di = 1.05, 0.78, 0.63, are tested. Cold and hot water are used as working fluids in the shell side and tube side, respectively. Experiments are performed under conditions of mass flow rates varying from 0.01 to 0.10 kg/s for cold water and from 0.01 to 0.10 kg/s for hot water, respectively. The inlet cold and hot water temperatures are between 15 and 20 °C and between 40 and 50 °C, respectively. The results obtained from the tubes with helical ribs are compared with those without helical ribs. It is found that the helical ribs have a significant effect on the heat transfer and pressure drop augmentations. Based on fitting the experimental data, non-isothermal correlations of the heat transfer coefficient and friction factor are proposed. The majority of the data falls within ±15%, ±15% of the proposed correlations for heat transfer coefficient and friction factor, respectively. © 2006.
dc.format.mimetypeapplication/pdf
dc.identifier.citationEnergy Conversion and Management. Vol 47, No.18-19 (2006), p.3031-3044
dc.identifier.doi10.1016/j.enconman.2006.03.023
dc.identifier.issn1968904
dc.identifier.other2-s2.0-33745885927
dc.identifier.urihttps://hdl.handle.net/20.500.14740/5332
dc.rights.holderมหาวิทยาลัยศรีนครินทรวิโรฒ
dc.subject.otherData acquisition
dc.subject.otherHeat pipes
dc.subject.otherHot water heating
dc.subject.otherParameter estimation
dc.subject.otherPressure drop
dc.subject.otherSuperheater tubes
dc.subject.otherThermal effects
dc.subject.otherFriction factor
dc.subject.otherHeat transfer coefficient
dc.subject.otherHelical rib
dc.subject.otherHeat transfer
dc.titleTube side heat transfer coefficient and friction factor characteristics of horizontal tubes with helical rib