Publication: Study on Installation of Neutral Ground Resistance in Very Small Power Plant Transformer
0
0
Issued Date
2022
Resource Type
Language
eng
File Type
application/pdf
ISSN
1972618
Rights Holder(s)
Scopus
Bibliographic Citation
Kasetsart Journal of Social Sciences. Vol 43, No.4 (2022), p.867-872
Suggested Citation
Chiradeja P., Pothisarn C., Srisuksai P., Yoomak S., Ngaopitakkul A., Phannil N. Study on Installation of Neutral Ground Resistance in Very Small Power Plant Transformer. Kasetsart Journal of Social Sciences. Vol 43, No.4 (2022), p.867-872. doi:10.1109/IAS54023.2022.9939721 Retrieved from: https://hdl.handle.net/20.500.14740/10000
Abstract
Faults in the distribution system of the Thai electrical system occur frequently. Such faults directly affect the protective equipment of the distribution system. The protective device disconnects the circuit unnecessarily on many occasions because it detects a higher current than expected. In this study, a 22-kV distribution system and a very small power plant (VSPP) were connected. The system consists of two feeders. Feeder 1 supplies electricity directly to the load; a fault was enforced in this feeder. Feeder 2 supplies electricity directly to the load; the VSPP was connected to this feeder. The fault in Feeder 1 was simulated, and the behavior of the defense system was studied. Unnecessary disconnection of the VSPP circuit took place because the high fault current caused the overcurrent protection relay to operate instantaneously. Therefore, a neutral ground resistance was installed at the VSPP transformer to reduce the fault current, extend the relay operating time to the delay range, and reduce unnecessary disconnections of the overcurrent protection relay of the VSPP. In addition, when a fault occurs in the distribution system, the faulted phase voltage decreases, whereas the non-faulted phase voltage increases. Surge arresters and voltage transformers must be able to withstand an increase in voltage. This is also explained and discussed in this paper. © 2022 IEEE.