ชื่อเรื่อง: Electric field minimization using optimal phase arrangement techniques for MEA overhead power transmission lines
ผู้แต่ง: Nunchuen S.
Halapee J.
Tarateeraseth V.
Keywords: Electric fields
MATLAB
More electric aircraft
Power transmission
MATLAB program
Measured results
Phase arrangement
Simulated results
World Health Organization
Electric lines
วันที่เผยแพร่: 2019
บทคัดย่อ: In order to minimize the electric field generated by Metropolitan Electricity Authority (MEA) overhead power transmission lines, the optimal phase arrangement techniques were applied for 3-circuits overhead power transmission lines (69/230 KV. In this paper, the mathematical model was designed using a MATLAB program which validated by comparing the simulated results with the measured results where the South Thonburi power transmission lines at Rama 2 Road (outbound side) were evaluated with the same conditions. Finally, it can be concluded that the optimal phase arrangement techniques can minimize the generated electric field lowering than that of the limitation given by the World Health organization. © 2019 IEEE.
URI: https://ir.swu.ac.th/jspui/handle/123456789/12379
https://www.scopus.com/inward/record.uri?eid=2-s2.0-85078856423&doi=10.1109%2fECTI-CON47248.2019.8955173&partnerID=40&md5=56bfa2a55eb5d5b93851eaaa0da53d22